Αντικεραυνικό 3P 20kA 1000V Type 1+2 DC Φωτοβολταϊκά 64310
T1+T2 three-module photovoltage surge protective device (SPD) (with three -step DC switching device) features visual indication and optional remote contact signaling (floating changeover contact) for use in PV systems.
Technical data
- SPD classification according to IEC/EN61643-31: T1+T2
- Max. continuous operating a.c.voltage Ucpv: 1000V DC
- Impulse Discharge Current Iimp (10/350 μs): 6.25kA
- Total Discharge Current Itotal (10/350 μs): 12.5kA
- Nominal discharge current In (8/20μs): 20kA
- Maximum discharge current Imax (8/20μs): 40kA
- Voltage protection level DC+/DV-to PE: ≤5.2kV
- Response time: ≤25ns
- Operating temperature range (Tu): -40º~80º
- Operating State/Fault Indication: Green/Red
- Cross-section area (Min.): 4 mm2
- Cross-section area (Max.): 35 mm2
- Enclosure material: Thermal Plastic UL94-V0
- Ingress Protection: IP20