Επιτηρητής Τάσης Ράγας Μονοφασικός Ψηφιακός 41906
Technical Data
- Operated voltage range: 80-400V AC, 50/60Hz (Single-phase)
- Rated current: 63A
- Over-voltage protection value: 230-300V AC
- Under-voltage protection value: 140-230VAC
- Over-current protection value: 1-63A
- Voltage power off time: 0-400s
- Current power off time: 0-30s
- Voltage range setting step: 1V
- Time range setting step: 1s
- Power consumption: ≤ 1.5W
- Mechanical life: 100 000
- Relative humidity: 45-90% Rh
- Altitude: up to 2000m
- Pollution level: 2 class
- Dimensions: 36x80x66mm
- Mounting: on DIN rail
Factory Setting
- Over-voltage trip value: 270V
- Under-voltage trip value: 170V
- Over-current trip value: 63A
- Voltage power off time: 2s
- Starting delay time: 2s
- Current power off time: 2s